ESSER » Fire Systems » IQ8Control » IQ8Control M/Intelligent Addressable » FACP IQ8Control M
FACP IQ8Control M
The IQ8Control M as an efficient fire alarm control panel (FACP) for the property supervision of mid-sized to large objects, facilitates simultaneous detection, control and alarm signaling both on the analog ring as well as on the spur.
The loop operation type of the panel (powered-loop or non-powered-loop) can be selected via a jumper located on the power supply card.
Depending on which loop operation type has been selected, the corresponding analog module/modules should be used.
Features
- Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus analog loop modules (system supports up to 635 digital loop addresses in total)
- Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus analog loop modules (system supports up to 889 digital loop addresses in total)
- Short circuit and open circuit tolerant loop operation
- Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
- Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
- Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
- Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
- Fire brigade operating panel and transmission interface on the peripheral module
- Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
- TTY or RS 485 or RS 232 interface
- Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
- Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
- Operating panel with alphanumerical display
- Large display with 8 rows with 40 characters. As follows rated - four rows with 40 characters for the status information (first and last message), and the other four rows with 40 characters are used for system information e.g. “Sounders Off”
- Event memory for up to 10,000 events
- All Systems 8000 micromodules are compatible
- Printer interface for internal printer
- Two batteries with monitoring circuit
- Monitored input for external power supply unit
- Additional features for powered loop
- Max. 6 analog powered loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
- esserbus PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
- Up to 48 powered loop base sounders (series 9200) per loop
- Up to 32 powered loop IQ8Alarm per loop
- Up to 48 IQ8Quad with alarm device per loop
Technical Data
| Rated voltage |
230 V AC |
| Rated current |
0.35 A (standard); 0.7 A (powered loop) |
| Output voltage |
12 V DC |
| Quiescent current |
approx. 215 mA (basic configuration without operating unit)
approx. 230 mA (basic configuration with operating unit)
|
| Current consumption for ext. devices |
2 A |
| Battery capacity |
max. 2 x 12 V/24 Ah |
| Ambient temperature |
-5 °C ... 45 °C |
| Type of protection |
IP 30 |
| Housing |
ABS, 10 % glass fiber reinforced, V - 0 |
| Air humidity |
< 95 % (non condensing) |
| Color |
gray similar to Pantone 538 |
| Dimensions |
W: 450 mm H: 640 mm D: 185 mm |