Esser Fire Systems | Esser Management System | Esser Voice Alarms | Esser Loudspeakers | Gent Analoque Addressable | Gent Detection & Alarm Devices | Gent Interfaces | Gent Text & Graphic Software |
ESSER » Fire Systems » FlexES Control » FlexES Control/Intelligent Addressable » FlexES Control FX10 » FlexES Control FX10

FlexES Control FX10

Hardware FlexES Control FX10 basic configuration, with software support for 10 loops. System supports up to 1,270 digital loop addresses in total. 



Features

pp

Master/slave CPU by redundant control module

Combinable loop/spur technology with decentralized intelligence

Freely configurable functionality of modules

4 free programmable potential free contacts and 1 output for alarm transmission unit (ATU)

Increased availability via emergency mode function of the loop modules

Emergency mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the German Planning standard VDE 0833 and/or VdS 2095.

USB, RS 485, TTY interfaces onboard

Direct output of the proprietary EDP communications protocol (Data Protocol) via interface RS 485

Operation of loop-powered alarm signaling devices (optical/acoustic/voice) in different alarm zones via esserbus-PLus

Cascadable power supply to 450 W according to EN 54-4

Loop length up to 3.5 km (esserbus)

Operation of different input/output gateways

Integrated interfaces for operation of required fire brigade periphery, e.g. fire brigade indicating panel, fire brigade operating unit

Event memory with 10,000 entries

Operation of VdS-approved wireless components with convenient field intensity measurement

Parameterization, calibration and programming directly via USB

Galvanic isolation of analog loops possible

Up to 1,000 control zones 

In connection with display and operating unit (Part No. FX808324)

Display and operating unit with 5.7" TFT display

Capacitive keyboard for touch-sensitive operation

Program-controlled night design with interactive keyboard menu

Additional features for powered loop

BUS supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404

Up to 48 powered loop base sounders (series 9200) per loop

Up to 32 powered loop IQ8Alarm per loop

Up to 48 IQ8Quad with alarm device per loop

Technical Data

Rated voltage 230VAC
Rated frequency 50 ... 60 Hz
Rated current 0.8 A
Output voltage 24VDC
Quiescent current approx. 192 mA (base model w/o display and operating unit)
  approx. 348 mA (base model with display and operating unit)
Current consumption for ext. devices  3 A
Battery capacity 4 x 12 V / 24 Ah
Ambient temperature -5 °C ... 45 °C
Storage temperature -10 °C ... 50 °C
Type of protection IP 30
Housing ABS, 10% glass fiber reinforced, V - 0
Air humidity < 95 % (non condensing)
Color gray, similar to Pantone 538
Weight approx. 15.1 kg (incl. neutral front)
  approx. 17 kg (incl. operating unit)
Dimensions W: 450 mm H: 960 mm D: 185 mm