Automatic heat detector with a single thermistor to sense the air temperature around the detector. Fast semiconductor sensor guarantees reliable detection of fires with strong heat generation. Ideal for sensing in environments that are dirty or smoky under normal conditions, as well it is unaffected by wind or atmospheric pressure. Intelligent fire detector with decentralized intelligence, automatic function self-test, CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A remote indicator can be connected.
| Operating voltage | 8 ... 42 V DC |
| Quiescent current @ 19 V DC | approx. 40 μA |
| Alarm current w/o communication curtain | approx. 18 mA |
| Area to be monitored | max. 30 m² |
| Height to be monitored | max. 7.5 m |
| Air velocity | 0 ... 25.4 m/s |
| Application temperature | -20 °C ... 50 °C |
| Storage temperature | -25 °C ... 75 °C |
| Type of protection | IP43 (with base + option) |
| Material | ABS |
| Air humidity | < 95 % (non condensing) |
| Color | white, similar to RAL 9010 |
| Weight | approx. 110 g |
| Detector specification | EN 54 - 5 A1S / -17 |
| Dimensions | Ø: 117 mm H: 49 mm (62 mm incl. base) |