The small compact fully addressable (esserbus) intrinsically safe MCP version has detector housing, surface mount housing, transparent cover, and alarm indicator. For use in the esserbus® and powered loop with soft address coding, alarm latch and alarm indicators. The detector operates like a conventional MCP without the bus connection.
IQ8MCP without loop isolator, especially for use in ex-areas.
Suitable for use in damp rooms thanks to the high IP 66/67 IP protection.
Surface mounting housing is provided with break-out cable entries for M20 cable glands (optional) for easy installation.
| Operating voltage | 8 ... 30 V DC |
| Alarm current @ 9 V DC | typ. 9 mA |
| Alarm display | red LED and yellow actuation indicator |
| Operation indicator | LED, green |
| Ambient temperature (Ta) | -20 °C ... 70 °C |
| Application temperature | -20 °C ... 70 °C |
| Storage temperature | -30 °C ... 75 °C |
| Max. Output current (Io) | 10 mA |
| Max. Input Voltage (Ui) | 21 V DC |
| Max. Input current (Ii) | 252 mA |
| Max. internal capacity (Ci) | 1 nF |
| Explosion protection | Ex ib IIC T4 Gb |
| Connection terminal | max. 1,5 mm² (AWG 30-14) |
| Type of protection | IP 66, IP 67 |
| Housing | PC ASA plastic |
| Air humidity | < 95 % (non condensing) |
| Color | red, similar to RAL 3020 |
| Weight | approx. 255 g |
| Dimensions | W: 88 mm H: 88 mm D: 63 mm (with surface mount housing) |