The Vigilon Mains Powered Interface allows you to connect to ancillary units which can not be integrated directly onto the Vigilon loop
• 4 channel interface integrates with EN54:part 4 power supply
• A cost effective solution as all elements are included within the enclosure therefore reducing your installation and maintenance costs
• Four channels can be individually programmed to provide various configuration modes to control external equipment
| Operating voltage | 230V 50Hz +10% -6% |
| Current Consumption | 0.7A |
| Maximum number per loop | 100 units per loop (only 8 with fully sectored outputs) |
| Input modes | Input can be fault monitored, voltage free contacts OR conventional detection |
| Quiescent current | 20mA per zone (default) Zone short circuit current limited to < 30mA EN54 compliance limitation: 32 devices OR Maximum of 20 diode bases per zone |
| Output modes | Outputs are monitored 24V (nominal) 0.5A OR LED drive. Refer to the commissioning information for more details |
| Maximum total output current | 1.5A |
| Auxiliary power output | 24V +/- 3V (12V for S4-34440-12) |
| Storage temperature | 20º C to 70º C |
| Ambient operating temperature | 10º C to 45º C |
| Relative humidity (non condensing) | Up to 95% Temperature 5º C to 45º C |
| Ingress protection (estimated) | IP 31 |
| Enclosure | Steel |
| Colour | RAL7024 Graphite Grey (fine textured) |
| Overall dimensions | 478mm x 322mm x 128mm |
| Weight | 7Kg (excluding batteries and optional components fitted) |