ESSER » Fire Systems » IQ8Control » IQ8Control C/Intelligent Addressable » FACP IQ8Control C
FACP IQ8Control C
The IQ8Control C is an efficient fire alarm control panel for the property supervision of small to mid-sized objects facilitates simultaneous detection, control and alarm signaling both on the analog ring as well as on the spur.
Within the multi-functional IQ8Control C panel, the operation type (powered-loop or non-powered-loop) can be selected via a jumper located on the control panel power supply unit.
Depending on which loop operation type has been selected, the corresponding loop module/modules are required.
Features
- Max. two micromodules (system supports up to 254 digital loop addresses in total)
- Max. two esserbus analog loop modules
- Short circuit and open circuit resistant loop operation
- Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
- Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
- Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
- Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
- Fire brigade operating panel and alarm transmission unit interface on the peripheral module
- Three common relays, freely programmable, monitored, floating for up to 24 V DC/1A (on the peripheral module)
- TTY or RS 485, RS 232 interface
- Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
- Connection to graphical supervisor FlexES Guard/WINMAG via serial essernet interface (SEI)
- Operating panel with alphanumerical display
- Large display with 8 rows with 40 characters. As follows rated - four rows with 40 characters for the status information (first and last message), and the other four rows with 40 characters are used for system information e.g. “Sounders Off”
- Event memory for up to 10,000 events
- All System 8000 micromodules are compatible
- Printer interface for internal printer
- Two batteries with monitoring circuit
- Monitored input for external power supply unit
Additional features for powered loop
- Max. 2 analog powered loop modules (System supports up to 254 digital loop addresses in total)
- BUS powered, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54-3 with alarm tone as per DIN 33404
- Up to 48 powered loop base sounders (series 9200) per loop
- Up to 32 powered loop IQ8Alarm per loop
- Up to 48 IQ8Quad with alarm device per loop
Technical Data
| Rated voltage |
230 V AC |
| Rated frequency |
50 ... 60 Hz |
| Rated current |
0.35 A (standard); 0.7 A (powered loop) |
| Quiescent current |
approx. 215 mA (basic configuration without operating unit) approx. 230 mA (basic configuration with operating unit) |
| Current consumption for ext. devices |
2 A |
| Ambient temperature |
-5 °C ... 45 °C |
| Storage temperature |
-5 °C ... 50 °C |
| Type of protection |
IP 30 |
| Housing |
ABS, 10 % glass fiber reinforced, V - 0 |
| Color |
gray similar to Pantone 538 |
| Weight |
approx. 6.5 kg |
| Dimensions |
W: 450 mm H: 320 mm D: 185 mm |
Accessories