Vigilon Compact 1-2 loop panel offers small to medium sized building owners the unique system functionality of Vigilon with the very best in control panel aesthetics.
Part No. : COMPACT-24-N
Advanced loop card technology supporting 2km loop with standard 1.5mm2 cable (increases to 2.5km with 2.5mm2 cable)
Vigilon Compact is a 1 to 2 loop panel which manages up to 200 devices per loop
High capacity for loop powered alarm devices with up to 800mA alarm load or 100 integrated sensor sounder and visual alarm devices
PC based commissioning tools allow complex fire plans to be configured
Zonal LED indication on every panel provides compliance with BS 5839 Part 1: 2002
Serial communication ports allow connectivity to paging and BMS systems with no additional interface hardware
The control panel has a simple user interface with LCD screen providing accurate information in an emergency
Multiple panel networks can be programmed seamlessly as one system, allowing for flexible design and system management
Flexible programming options are available at the panel
| Max Number of Loops | 2 |
| Loop Capacity | 200 Devices per loop, Alarm load 800mA per loop (max across both loops 1.4A) |
| Networking Capacity | Up to 31 panels in a single domain (multiple domains can extend a network up to 200 panels) |
| Ingress Protection | IP 31 |
| Weight | Approx. 16.6 Kg (including batteries) |
| Operating Temperature | 0ºC to +45ºC |
| Batteries | 2 x 12V @ 12Ah |
| Battery Standby | 24 Hours + 30 minutes alarm (Dependant on device loading – please use the battery standby calculator to confirm actual standby) |
| Supply Voltage | 216V – 253V 50Hz |
| Power Consumption | 140 W |
| Aux DC supply | 24V 200 mA (must be considered when calculating battery standby) |
| Dimensions (mm) | 403 (H) x 338 (W) x 101 (D) |
| Auxiliary Contacts | Programmable to activate on Fire, Fault or Disablement. (1 x SPCO 1 x DPCO) |
| Sounder Circuits | 2 circuits @ 250mA each |
| Monitored input | 1 input which is programmable to perform a logical action via a command build |
| Communication ports | 1 x RS485 |
| 2 x RS232 |